Restaurant · Electrical

Al Sahafa restaurant: kitchen breakers tripping every evening

Every night between 8 and 10pm the kitchen went dark, taking two chillers and a freezer with it.

38 APeak load on a 32 A circuit
2Nights of work after closing
0Trips in the following 6 months

A commercial kitchen is a load-management problem disguised as an electrical one. Equipment is added one machine at a time — a second fryer here, a display chiller there — and each addition is small enough to seem harmless. Nobody recalculates the total, and eventually the sum of the small additions exceeds what the original circuit was designed to carry. The breaker then does exactly what it was installed to do.

The load survey

EquipmentMeasured currentOn the same circuit
Display chiller6 AYes
Walk-in freezer11 AYes
Double fryer13 AYes
Extract fan + lighting8 AYes
Total at peak38 AOn a 32 A breaker

The trips happened between 8 and 10pm because that is the only time all four ran together.

Measured current across the evening

Amps on the kitchen circuit against the 32 A breaker rating
0112334456pm7891011
Measured loadBreaker rating

What we changed

  • Refrigeration moved to its own dedicated circuit, so cooking equipment can never take the chillers down with it.
  • The distribution board upgraded with correctly sized breakers and an RCD on the wet area.
  • Fryers placed on a separate circuit with its own isolator.
  • A written safety report issued for the municipality file and the insurer.
Never solve tripping by fitting a bigger breaker. That removes the protection while leaving the overload in place — and it is the single most common cause of electrical fires in commercial kitchens.

Questions about this case

Can this work be done without closing the restaurant?

Yes. We work after closing, in stages, so the kitchen is fully operational at every opening. This job took two nights.

How do I know my kitchen is overloaded before it trips?

Warm socket faceplates, lights dimming when a compressor starts, and a breaker that feels hot are all early signs. A load survey measures it properly in under an hour.

Do you issue documentation for inspections?

Yes — a written report listing circuits tested, measured loads, breaker sizes and parts replaced.